IPM-IM-FRD DC Insulation Recording Device

IPM-IM-FRD DC insulation recording device is an online monitoring and protection equipment for smart substations. This device integrates DC insulation monitoring and recording functions, accurately capturing key voltage, current, and switch status data before and after DC power faults. It plays a crucial role in analyzing DC power faults.

Share to:

  • Insulation monitoring
  • Transient and steady-state recording functions
  • DC cross-talk detection calculation
  • AC cross-talk detection calculation
  • 500 dynamic fault data records
  • 5% precision monitoring of voltage and current data
  • Power failure saves 1000 historical alarm records
  • 1152 branch monitoring
  • Regular self-check
Measuring range
Bus voltage 0V-300V
Bus voltage to ground -300V-300V
Bus resistance to ground 0-999kΩ
Branch resistance to ground 0-999kΩ
ACintrusion voltage 0-250V
DC mutualintrusion resistance 0-200kΩ
Battery voltage 0-350V
Battery current 0~400A
Load current 0~400A
Measuring accuracy
Bus voltage to ground 0.5%(10%Un-1.3Un)
Branch leakage current 5%±0.1mA
Bus resistance to ground 2%±1k (resistance to ground:0~100kQ); 5%±1k (resistance to ground: 100~ 200k Q)
Branch resistance to ground 5%±2k0 (resistance to ground:0~100kn);10%±2kQ(resistance to ground; 100~200ko
AC intrusion voltage ±1%(10~250), specific valus should be displayed (<10V)
DC intrusion resistance 10%±2kQ (0-50kQ)
Battery voltage (0.5%*reading+0.1V)
Battery current (1%*reading+0.5A)
Load current (1%*reading+0.5A)
Other technical indexes
Recording frequency 4KHZ-10KHZ,adjustable
Recording channel Eight Al analog channels and eight Dl channels
Trigger data recording start mode (the following start conditions can be configured)
Sudden change start Including control bus voltage sudden change start, battery voltage sudden change startbattery curent sudden change start
Out-of-limit star Including control busvoltage out-of-limit start, battery voltage out-of-limit start, control busnegative voltage to ground; out-of-limit, control bus AC negative voltage to ground out-of-limitbattery charging current sudden change out-of-limit, battery discharge current out-of-limit
Continuous data recording
Data recording interval 1s
Maximum recording time 120d
Recording format Universal power recording format: comtrade99, cyclic coverage update
Support the functions of RiG-B code clock synchronization and B code forwarding
16-bit 200 KSPS sampling rate per channel ADC detection
Display 7 inches,1024*600, true color LCD capacitive screen
8GB large storage capacity